Model DM-434B
Oxygen Deficiency Sensor (0-25% O2)
Operator’s Installation & Instruction Manual
October 21, 2008 • Document #2021T • Version 1.7
CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED
AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND
INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING OR SERVICING.
ATTENTION: POUR DES RAISONS DE SECURITE, CET EQUIPEMENT DOIT ETRE
UTILISE ENTRETENU ET REPARE UNIQUEMENT PAR UN PERSONNEL QUALI-
FIE. ETUDIER LE MANUEL D'INSTRUCTIONS EN ENTIER AVANT D'UTILISER,
D'ENTRETENIR OU DE REPARER L'EQUIPEMENT.
detcon inc.
Vue de la page 0
1 2 3 4 5 6 ... 10 11

Résumé du contenu

Page 1 - Model DM-434B

Model DM-434BOxygen Deficiency Sensor (0-25% O2)Operator’s Installation & Instruction ManualOctober 21, 2008 • Document #2021T • Version 1.7CAUTIO

Page 2 - Table of Contents

7.2 Calibration1) Declassify the area around the sensor.2) Remove the junction box cover.3) Measure the voltage between signal test points. If neces

Page 3 - 1.0 DESCRIPTION

9.0 WARRANTYDetcon, Inc., as manufacturer, warrants each new O2 plug-in sensor cell, for a two year period under theconditions described as follows:

Page 4 - Terminals

Table of Contents1.0 Description2.0 Principle of Operation3.0 Application4.0 Specifications5.0 Installation6.0 Start-up7.0 Calibration8.0 Spare Parts

Page 5 - 2.0 PRINCIPLE OF OPERATION

1.0 DESCRIPTIONDetcon Model DM-434B, oxygen sensors are designed to detect and continuously monitor O2 in air over therange of 0-25%. Method of dete

Page 6 - 5.0 INSTALLATION

1.3 Terminal BoardThe terminal board is mounted in the explosion proof enclosure and includes: the mating connector for thecontrol circuit, reverse i

Page 7 - Figure #2

2.0 PRINCIPLE OF OPERATIONMethod of detection is by a controlled rate of diffusion. Air and gas diffuse through a sintered stainlesssteel filter and

Page 8 - Term ina ls

Linearity± 0.5% FSOutputLinear 4-20 mA DCInput Voltage11.5-28 VDCPower Consumption< 0.6 wattsElectrical ClassificationClass I; Groups B, C, D; Div.

Page 9 - 7.0 CALIBRATION PROCEDURE

by facility engineers with experience in similar processes.Ventilation - Normal ventilation or prevailing wind conditions can dictate efficient locati

Page 10 - 8.0 SPARE PARTS LIST

c) Terminate 2 conductor field wiring to the sensor terminal board observing correct polarity in accor-dance with the detail shown in figure 3.d) Repl

Page 11 - 10.0 SERVICE POLICY

6.0 START UPUpon completion of all mechanical mounting and termination of all field wiring, apply system power andobserve the following normal condit