This is the trip point for the first alarm.
Register #
High Byte Low Byte
40004 Alarm 2 Setpoint
This is the trip point for the second alarm.
Register #
High Byte Low Byte
40005 Status Bits Status Bits
High Byte
Bit 7 Not used, always 0
Bit 6 Not used, always 0
Bit 5 Not used, always 0
Bit 4 Not used, always 0
Bit 3 1-Unit is in calibration 0-Normal operation
Bit 2 1-Alarm 2 is ascending 0-Alarm 2 is descending
Bit 1 1-Alarm 2 is normally energized 0-Alarm 2 is normally de-energized
Bit 0 1-Alarm 2 is latching 0-Alarm 2 is non-latching
Low Byte
Bit 7 1-Alarm 2 Relay is energized 0-Alarm 2 Relay is not energized
Bit 6 1-Alarm 1 is ascending 0-Alarm 1 is descending
Bit 5 1-Alarm 1 is normally energized 0-Alarm 1 is normally de-energized
Bit 4 1-Alarm 1 is latching 0-Alarm 1 is non-latching
Bit 3 1-Alarm 1 Relay is energized 0-Alarm 1 Relay is not energized
Bit 2 1-Fault is normally energized 0-Fault is normally de-energized
Bit 1 1-Fault is latching 0-Fault is non-latching
Bit 0 1-Fault Relay is energized 0-Fault Relay is not energized
The following is a typical Master Query for device # 8:
Field
Name HEX DEC RTU
Slave Address 08 8 0000 1000
Function 03 3 0000 0011
Start Address Hi 00 0 0000 0000
Start Address Lo 00 0 0000 0000
No. of Registers Hi 00 0 0000 0000
No. of Registers Lo 06 6 0000 0110
CRC ## #### ####
CRC ## #### ####
The following is a typical Slave Response from device # 8:
Field
Name HEX DEC RTU
Slave Address 08 8 0000 1000
Function 03 3 0000 0011
Byte Count 0C 12 0000 1100
Reg40000 Data Hi 02 2 0000 0010
Reg40000 Data Lo 64 100 0110 0100
Reg40001 Data Hi 00 0 0000 0000
Reg40001 Data Lo 64 100 0110 0100
Reg40002 Data Hi 00 0 0000 0000
Model FP-624C Combustible Gas Sensor PG.22