detcon inc.
Detcon MicroSafe
IR-522 Combustible Hydrocarbon Sensor (0-100% LEL)
Operator’s Installation & Instruction Manual
December 2, 2013 • Document #2272 • Version 1.4
CAUTION:
Before operating the Model IR-522 sensor, read this manual thoroughly and verify that the con-
figuration of default factory settings are appropriate and correct for your application.
Vue de la page 0
1 2 3 4 5 6 ... 18 19

Résumé du contenu

Page 1 - Detcon MicroSafe

detcon inc.Detcon MicroSafe™IR-522 Combustible Hydrocarbon Sensor (0-100% LEL)Operator’s Installation & Instruction ManualDecember 2, 2013 • Docum

Page 2 - Table of Contents

3.5.5 Remote Mounting ApplicationsSome sensor mounting applications require that the gas sensor head be remotely mounted away from the sensortransmit

Page 3 - 3.0 DESCRIPTION

3.6 START UPUpon completion of all mechanical mounting and termination of all field wiring, apply system power and observethe following normal condit

Page 4 - Base Connector Board

A magnetic programming tool (see figure 5) is used to operate the switches. Switch action is defined as momentarycontact, 3 second hold, and 30 second

Page 5 - 3.1 PRINCIPLE OF OPERATION

NOTE 2: When a “cal fault” occurs, the sensor microprocessor retains its previous calibration references.Zero calibration is complete.3.7.2 Calibrati

Page 6 - Output Response Curve

3.7.3 Additional Notes1. Upon entering the calibration menu, the 4-20 mA signal drops to 2 mA and is held at this level until youreturn to normal ope

Page 7 - 3.4 OPERATING SOFTWARE

Calibration FaultIf during calibration the sensor circuitry is unable to attain the proper adjustment for zero or span, the sensor willenter into the

Page 8 - 3.5 INSTALLATION

3.11 OPTICAL SENSOR REPLACEMENT PROCEDUREShould the optical gas sensor element (part number 370-365871-212) require replacement, use the following pr

Page 9 - Figure #1

Bad 4-20 mA output1. Check that wiring is connected to correct terminal outputs. 2. Swap with a known-good transmitter to determine if transmitter is

Page 10 - Figure #2

3.14 WARRANTYDetcon, Inc., as manufacturer, warrants each NDIR optical plug in sensor (part no. 370-365871-212), for a pro-ratedfive year period unde

Page 11 - Material Requirements

3.16 SOFTWARE FLOW CHART3.17 REVISION LOGRevision Date Approval Changes Made1.3 11/28/07 LU Section 3.6.1a and 3.7.2g flow rate changed from “500-1,00

Page 12

Table of Contents3.0 Description3.1 Principle of Operation3.2 Application3.3 Specifications3.4 Operating Software3.5 Installation3.6 Start-up3.7 Calib

Page 13

3.0 DESCRIPTIONDetcon MicroSafe™ Model IR-522, combustible hydrocarbon gas sensors are non-intrusive “Smart” sensorsdesigned to detect and monitor co

Page 14 - 3.9 PROGRAM FEATURES

3.0.2 Microprocessor Control CircuitThe control circuit is microprocessor based and is packaged as a plug-in field replaceable module, facilitating e

Page 15 - 3.10 DISPLAY CONTRAST ADJUST

3.0.4 Explosion Proof EnclosureThe sensors are packaged in a cast metal explosion proof enclosure. The enclosure is fitted with a threaded coverthat

Page 16 - 3.12 TROUBLE SHOOTING GUIDE

tained, excessive loss in useable signal eventually gives way to noise and unstable readings. The optical sensor may, over longperiods of time (3-7 ye

Page 17 - 3.13 SPARE PARTS LIST

Electrical ClassificationClass I; Groups B, C, D; Div. 1.Response TimeT50 < 15 seconds; T90 < 35 secondsClearing Time90% < 35 secondsRepeatab

Page 18 - ERVICE POLICY

3.4.3 Program ModeThe program mode provides a program status menu, allows for the adjustment of alarm set point levels, and theselection of the calib

Page 19 - OPERATION

Density - Placement of sensors relative to the density of the target gas is such that sensors for the detection ofheavier than air gases should be loc