Detcon 240 Manuel d'instructions Page 22

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 33
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 21
240 Operators Manual
Model 240 Operator Manual Rev. 1.8 Page 18 of 29
7. System Features
7.1 Modbus Communications
The model 240 controller features a Modbus compatible communications protocol and is addressable by a
PLC, PC/HMI, DCS, or other Modbus RTU master polling device. Communications is accomplished by
two wire half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, through the controllers secondary
port. Wiring should be brought directly to J10 located on the motherboard.
A Modbus™ RTU master device up to 4000 feet away can theoretically poll up to 64 different controllers.
This number may not be realistic in harsh environments where noise and/or wiring conditions would make
it impractical to place so many devices on the same pair of wires. If a multi-point system is being utilized,
each controller must be set to a different device address.
Modbus™ Register Detail:
Code 03 - Read Holding Registers is the only code supported by the 240 controller.
Register #
40000 Channel 1 Reading
40001 Channel 2 Reading
40002 Fault Status Bits
High Byte
Bit 7 Not Used
Bit 6 Not Used
Bit 5 Not Used
Bit 4 Not Used
Bit 3 Not Used
Bit 2 Not Used
Bit 1 Not Used
Bit 0 Not Used
Low Byte
Bit 7 Not Used
Bit 6 Not Used
Bit 5 Not Used
Bit 4 Not Used
Bit 3 Not Used
Bit 2 Not Used
Bit 1 1 = Channel 2 Fault 0 = Channel 2 no Fault
Bit 0 1 = Channel 1 Fault 0 = Channel 1 no Fault
40003 Alarm 1 Status Bits
High Byte
Bit 7 Not Used
Bit 6 Not Used
Bit 5 Not Used
Bit 4 Not Used
Bit 3 Not Used
Bit 2 Not Used
Bit 1 Not Used
Bit 0 Not Used
Low Byte
Vue de la page 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 32 33

Commentaires sur ces manuels

Pas de commentaire